3-20 D30 LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
WIRING CHAPTER 3: INSTALLATION
3
For high-density input/output modules 6W and 6X, use the following guidelines to connect:
12 to 24 AWG (3.3 mm
2
to 0.2 mm
2
), single wire termination
16 to 24 AWG (1.31 mm
2
to 0.2 mm
2
), multiple wire termination with matching wire sizes and stranding. Two wires
maximum per circuit.
Suggested wiring screw tightening torque is a minimum 4.43 in-lb (0.5 Nm) and maximum 5.31 in-lb (0.6 Nm)
Minimum suggested temperature rating for the conductors is 75°C
Wire type: copper
Do not use with SL power supply module
Table 3-3: Contact input and output module assignments
Where a tilde “~” symbol appears, substitute the slot position of the module. Where a number sign “#” appears,
substitute the contact number.
When current monitoring is used to seal-in the form-A and solid-state relay contact outputs, give the
FlexLogic operand driving the contact output a reset delay of 10 ms to prevent damage of the output
contact (in situations when the element initiating the contact output is bouncing, at values in the
region of the pickup value).
~6A module ~6B module ~6C module ~6D module
Terminal
assignment
Output or
input
Terminal
assignment
Output or
input
Terminal
assignment
Output Terminal
assignment
Output
~1 Form-A ~1 Form-A ~1 Form-C ~1a, ~1c 2 Inputs
~2 Form-A ~2 Form-A ~2 Form-C ~2a, ~2c 2 Inputs
~3 Form-C ~3 Form-C ~3 Form-C ~3a, ~3c 2 Inputs
~4 Form-C ~4 Form-C ~4 Form-C ~4a, ~4c 2 Inputs
~5a, ~5c 2 Inputs ~5 Form-C ~5 Form-C ~5a, ~5c 2 Inputs
~6a, ~6c 2 Inputs ~6 Form-C ~6 Form-C ~6a, ~6c 2 Inputs
~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs ~7 Form-C ~7a, ~7c 2 Inputs
~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs ~8 Form-C ~8a, ~8c 2 Inputs
~6E module ~6F module ~6G module ~6H module
Terminal
assignment
Output or
input
Terminal
assignment
Output Terminal
assignment
Output or
input
Terminal
assignment
Output or
input
~1Form-C~1Fast Form-C~1 Form-A ~1 Form-A
~2Form-C~2Fast Form-C~2 Form-A ~2 Form-A
~3Form-C~3Fast Form-C~3 Form-A ~3 Form-A
~4Form-C~4Fast Form-C~4 Form-A ~4 Form-A
~5a, ~5c 2 Inputs ~5Fast Form-C~5a,
~5c 2 Inputs ~5 Form-A
~6a, ~6c 2 Inputs ~6Fast Form-C~6a, ~6c 2 Inputs ~6 Form-A
~7a, ~7c 2 Inputs ~7Fast Form-C~7a, ~7c 2 Inputs ~7a, ~7c 2 Inputs
~8a, ~8c 2 Inputs ~8Fast Form-C~8a, ~8c 2 Inputs ~8a, ~8c 2 Inputs
~6K module ~6L module ~6M module ~6N module
Terminal
assignment
Output Terminal
assignment
Output or
input
Terminal
assignment
Output or
input
Terminal
assignment
Output or
input
~1 Form-C ~1Form-A~1Form-A~1Form-A
~2 Form-C ~2Form-A~2Form-A~2Form-A

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE D30 and is the answer not in the manual?

GE D30 Specifications

General IconGeneral
BrandGE
ModelD30
CategoryRelays
LanguageEnglish

Related product manuals