RECONDITIONING
REV7 /REV7 OI 250 (EN) 101 / 146
Reassembly:
Replace all O-rings and gaskets.
Reverse the sequence to assemble the crankcase.
Insert a new filter bag (see “Replacing the Adsorption filter”
on Page 97).
Mount the interrupter chamber (see “Connecting the
Interrupter Chamber to the Post Insulator” on Page 95).
Remount the pole column on the base frame.
Re-commission the circuit breaker as described in the
commissioning section.
The following instructions must be followed when assembling
and installing the parts:
- Follow the specified lubrication procedure.
- Replace all seals and gaskets.
- Tighten the three screws (68) to a torque of 18Nm.
- Do not forget the filter sleeve (48).
- Do not install a new filter bag until right before evacuating the
assembled pole column.
CAUTION