COMMISSIONING
62 / 146 OI 250 (EN) REV7 /REV6
7.6.6 Manually Charging the Closing Spring
Check the operating state of the circuit breaker and the
mechanism:
- Closing spring discharged.
- Breaker either in closed or open position.
- Control voltage disconnected.
Open the door of the mechanism.
Using the hand crank (70.53), turn the gearing clockwise until the
spring position indicator shows "closing spring charged“.
In this position the gearing is in idling position and can be turned
further.
While the closing spring is being charged, the return stop
prevents the crank wheel from slipping backwards when manual
charging is interrupted or stopped.
Close the cabinet door.