INSTALLATION
REV7 /REV7 OI 250 (EN) 35 / 146
6.7 Mounting the Density Monitor and Filler Block to Pole B
• Mount the density monitor, filler block and bracket (1) using the
bolt (2), washer (3) and nut (4) at the specified position on the
lattice support (view X). Tighten to a torque of 25 Nm.
In breaker configurations with three density monitors, the list
below must be repeated for poles A and C. The design of the
mounting bracket for the density monitor may differ from the
picture shown below.
1 Density monitor, filler block and bracket 1x
2 Bolt, M8 x 20 A2-70 2x
3 Washer, 8.4 A2 2x
4Nut, M8 A2-70 2x