SLOW OPERATION FOR MAINTENANCE PURPOSES
REV7 /REV3 OI 250 (EN) 137 / 146
146
If Then
Spring mechanism has no under-
voltage release
Manual releases are normally
locked.
If this is not the case:
Loosen the M6 screws.
Slide manual release locking
device (7) in the direction of the
arrow until manual releases are
locked.
Retighten the M6 screws.
Spring mechanism has undervol-
tage release and integrated lok-
king device
Spring mechanism has undervol-
tage release but no locking de-
vice
The manual release locking de-
vice (7) is normally not installed in
this model.
Slide manual release locking
device (7) in the direction of the
arrow until manual releases are
locked.
Tighten the M6 screws.
Manual release locking device
7 Manual release locking device 9 Manual opening release
8 Manual closing release
9
7
8
M6