MA-003 – MULTITRANS User Guide – Rev 3.0  18-Jan-16  Page 5 of 30 
1  INTRODUCTION 
1.1  Product Overview 
The MULTITRANS™ (herein referred to as the product) is an  on-line DGA (Dissolved Gas 
Analysis)  system  for  transformer  diagnostics.  It  is  designed  to  monitor  up  to  three 
separate oil  tanks or  a  bank of three single-phase  transformers  in  close  proximity.  The 
product  measures  the  following  key  fault  gases  in  the  transformer  oil:  hydrogen, 
methane,  ethane,  ethylene,  carbon  monoxide,  carbon  dioxide  and  acetylene.  In 
addition the product also measures oxygen, nitrogen as well as moisture in the oil and 
the  transformer  load  current.  Such  data  provides  insight  on  transformer  condition 
criteria,  such  as  developing  faults,  paper  degradation  and  electrical  arcing.  Once 
installed, operation is straightforward. All results are stored within the product, but can be 
downloaded to a PC for analysis. 
The key features and characteristics are summarised as follows: 
  Utilises dynamic headspace sampling to extract target gases from the oil sample. 
  No consumables, such as carrier gases are required. 
  Accurate results are available as often as once per hour. 
  Minimal maintenance*. 
  Uses highly accurate and stable Photo-acoustic Spectrographic technology. 
  Fully  embedded  microprocessor  with  non-volatile  internal  memory  storage  for 
10,000 records. 
  Stainless  steel  outdoor-rated  IP55  enclosure  connected  to  the  transformer  by 
robust stainless steel tubing. 
  All gas sensing is carried out internally – no external gas sensors. 
  Transformer load tracking is available. 
  Six user-configurable relay contacts based on absolute gas and moisture values. 
  Two user-configurable sunlight-visible LED arrays on the exterior of the enclosure – 
one red for alarm, one yellow for caution. 
  Two standard sunlight-visible LED arrays – green for power, blue for service. 
  Communication  options  include:  Ethernet,  RS-232,  Cellular  modem  (GSM/GPRS), 
PSTN modem, RS-485 and Fibre Optic. Other options may be available on request. 
  Internal  USB  connection  provided  for  commissioning  and  service,  or  local  data 
download. 
*Note:  The  only  recommended  maintenance  is  periodic  cleaning  of  the  air  filters,  in-line  oil  filter  and 
battery replacement. 
1.2  Manual Scope 
This guide outlines the use of the LCD panel, manual DGA sampling function and general 
maintenance activities.