EasyManua.ls Logo

GE Kilsen KFP-CF4 - Connecting Zones and Devices

GE Kilsen KFP-CF4
76 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 2: Installation
Kilsen KFP-CF Series Installation Manual 9
Overview of fire system connections
Figure 4: Overview of fire system connections
Connecting zones and zone devices
Connecting zones
Connect zone wires as shown in Figure 4 above. Line resistance is shown in the table
below.
Zone type Line resistance
Mixed (automatic and manual) Max. 40
Automatic Max. 55
Manual Max. 55
Note: The default zone detection settings for each operating mode can be found in
Appendix A “Configuration presets” on page 59. To change the zone detection setting,
see “Advanced configuration” on page 31.
Terminating zones
Each zone circuit requires a 4.7 k end-of-line resistor for termination. If a zone is not
used, the 4.7 k end-of-line resistor must be installed across the unused zone
terminals.
Note: For BS 5839-1 the default zone configuration is active end-of-line and an active
end-of-line module must be installed instead of an end-of-line resistor. Unused zones
must be terminated with an active end-of-line module or configured as passive end-
of-line and terminated with a 4.7 k end-of-line resistor as described above.

Table of Contents

Related product manuals