Chapter 5: Technical specifications
52 Kilsen KFP-CF Series Installation Manual
Power supply specifications
Mains supply
Operating voltage 110 VAC / 60 Hz or 240 VAC / 50 Hz
Rated current (two- and four-zone control panels)
110 VAC
240 VAC
2 A
2 A
Rated current (eight-zone control panels)
110 VAC
240 VAC
3.15 A
1.5 A
Voltage tolerance +10% / 15%
Mains fuse
110 VAC
240 VAC
T 3.15A 250V
T 2A 250V
24 VDC power supply unit
Two- and four-zone control panels
DC voltage
Rated current
Current range
Rated power
Voltage tolerance
24 V
2 A
0 to 2 A
50 W
±2%
Eight-zone control panel
DC voltage
Rated current
Current range
Rated power
Voltage tolerance
24 V
4 A
0 to 4 A
100 W
±2%
Batteries and battery charger
Batteries
Two- and four-zone control panels
Eight-zone control panel
2 x 7.2 Ah
2 x 7.2 Ah or 2 x 12 Ah
Battery type Sealed lead-acid
Battery charger voltage 27.3 V at 20ºC 36mV/ºC
Battery charger current
Two- and four-zone control panels
Eight-zone control panel
Max. 0.5 A
Max. 0.7 A