GE Multilin M60 Motor Protection System 5-35
5 SETTINGS 5.2 PRODUCT SETUP
5
The serial communication ports utilize the Modbus protocol, unless configured for DNP operation (see descriptions below).
This allows the EnerVista UR Setup software to be used. The UR operates as a Modbus slave device only. When using
Modbus protocol on the RS232 port, the M60 responds regardless of the MODBUS SLAVE ADDRESS programmed. For the
RS485 port, each M60 must have a unique address from 1 to 254. Address 0 is the broadcast address which all Modbus
slave devices listen to. Addresses do not have to be sequential, but no two devices can have the same address or conflicts
resulting in errors will occur. Generally, each device added to the link should use the next higher address starting at 1. See
Appendix B for more information on the Modbus protocol.
A value of 0 closes the port. When the Modbus port is set to 0, communicate with the relay using the front panel or serial
port.
When a 0 value is involved in a change, the changes to the MODBUS TCP PORT NUMBER setting take effect
when the M60 is restarted.
h) PROTOCOL
Select among DNP3.0, IEC60870-104, and IEC60870-103, with DNP being the default. For any change to take effect,
restart the unit.
The table captures all possible combinations of protocols.
Table 5–5: PORT AND PROTOCOL COMBINATIONS
PROTOCOL PORT: CHANNEL RS232 RS485 ETHERNET
DNP Channel 1: Eth TCP
Channel 2: Eth TCP
Modbus Modbus DNP, Modbus, IEC 61850
Channel 1: Eth TCP
Channel 2: none
Modbus Modbus DNP, Modbus, IEC 61850
Channel 1: none
Channel 2: Eth TCP
Modbus Modbus DNP, Modbus, IEC 61850
Channel 1: Eth UDP
Channel 2: none
Modbus Modbus DNP, Modbus, IEC 61850
Channel 1: Eth TCP
Channel 2: RS485
Modbus DNP DNP, Modbus, IEC 61850
Channel 1: Eth TCP
Channel 2: RS232
DNP Modbus DNP, Modbus, IEC 61850
Channel 1: Eth UDP
Channel 2: RS485
Modbus DNP DNP, Modbus, IEC 61850
Channel 1: Eth UDP
Channel 2: RS232
DNP Modbus DNP, Modbus, IEC 61850
Channel 1: RS485
Channel 2: Eth TCP
Modbus DNP DNP, Modbus, IEC 61850
Channel 1: RS232
Channel 2: Eth TCP
DNP Modbus DNP, Modbus, IEC 61850
Channel 1: RS485
Channel 2: RS232
DNP DNP Modbus, IEC 61850
Channel 1: RS232
Channel 2: RS485
DNP DNP Modbus, IEC 61850
Channel 1: RS485
Channel 2: none
Modbus DNP Modbus, IEC 61850
IEC 104 Modbus Modbus IEC 104, Modbus, IEC 61850
IEC 103 Modbus IEC 103 Modbus, IEC 61850