EasyManua.ls Logo

GE M60 UR Series

GE M60 UR Series
662 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3-24 M60 Motor Protection System GE Multilin
3.2 WIRING 3 HARDWARE
3
3.2.10 IRIG-B
IRIG-B is a standard time code format that allows stamping of events to be synchronized among connected devices within
1 millisecond. The IRIG time code formats are serial, width-modulated codes that can be either DC level shifted or ampli-
tude modulated (AM). Third party equipment is available for generating the IRIG-B signal; this equipment can use a GPS
satellite system to obtain the time reference so that devices at different geographic locations can be synchronized.
Figure 3–24: OPTIONS FOR THE IRIG-B CONNECTION
Using an amplitude modulated receiver causes errors up to 1 ms in event time-stamping.