GE Multilin M60 Motor Protection System 6-27
6 ACTUAL VALUES 6.4 RECORDS
6
The starting capacity, starting current, and acceleration time values for the last start are displayed in ACTUAL VALUES STA-
TUS MOTOR menu. Clearing the motor data (refer to the Clear records section in chapter 7) resets these values to their
default.
Figure 6–4: MOTOR LEARNED DATA FUNCTIONALITY
6.4.4 EVENT RECORDS
PATH: ACTUAL VALUES RECORDS EVENT RECORDS
EVENT RECORDS
EVENT: XXXX
RESET OP(PUSHBUTTON)
MESSAGE
EVENT: 3
POWER ON
EVENT 3
DATE: 2000/07/14
MESSAGE
EVENT: 2
POWER OFF
EVENT 3
TIME: 14:53:00.03405
MESSAGE
EVENT: 1
EVENTS CLEARED
Date and Time Stamps
Motor running
(status)
Capture starting
thermal capacity
Idle
Capture starting
effective current n
STRT
I>0and
I < overload PKP
Capture acceleration
time
Capture thermal
capacity used
Motor stopped
(status)
Capture run time
after start
Store learned acceleration time
Store average run time after start
I
Run
=(I
n-1
Run
,...,I
n-N
Run
)/N
Every 1 minute -
capture load current
Store last acceleration time
Store learned thermal capacity used
Store last thermal capacity used
75
6
12
11
10
84
2
1
93
Store last starting current
Store learned starting current
75
6
12
11
10
84
2
1
93
No
Acceleration time
Successful start
1 minute
Yes
Motor starting
(status)
t
Nn
accel
n
accelaccel
tt
−
= ,...,max
II
I
Nn
start
n
start
start
−
=
,...,
marginTCUStart
TC,...,TCmaxTC
×
=
−Nn
learned
n
learnedlearned
avg
Nn
load
n
load
load
t
II
I
−
=
,...,sum
Store average load current every
interval and update displayt
avg
833724A1.CDR