GE Multilin M60 Motor Protection System 5-103
5 SETTINGS 5.4 SYSTEM SETUP
5
• SPEED2 MOTOR SOURCE: This setting selects source for a motor protection when two-speed motor functionality is
used. This can be separate voltage and current banks or one voltage and current bank one with different full load cur-
rent value at the second speed (entered in the SPEED2 MOTOR FLA setting). If separate CTs with different ratios or sec-
ondary currents are required for speed 2, then the relay should be ordered with two CT banks.
• SPEED2 MOTOR FLA: This setting specifies the motor full load current for speed 2.
Figure 5–26: TWO SPEED MOTOR CONNECTIONS
833723A1.CDR
MOTOR
T1
T2
T3
T4
T5
T6
L1
L2
L3
CT bank 2
Contact
outputs
L
L
L
H
H
H
M60 protection
and logic
H
L
STOP
HIGH
LOW
H
H
H
L
Contact inputs
CT bank 1