GE Multilin M60 Motor Protection System B-17
APPENDIX B B.4 MEMORY MAPPING
B
1D40 ...Repeated for Source 5
1D50 ...Repeated for Source 6
Energy Commands (Read/Write Command)
1D60 Energy Clear Command 0 to 1 --- 1 F126 0 (No)
Source Frequency (Read Only) (6 Modules)
1D80 Frequency for Source 1 2 to 90 Hz 0.001 F003 0
1D82 Frequency for Source 2 2 to 90 Hz 0.001 F003 0
1D84 Frequency for Source 3 2 to 90 Hz 0.001 F003 0
1D86 Frequency for Source 4 2 to 90 Hz 0.001 F003 0
1D88 Frequency for Source 5 2 to 90 Hz 0.001 F003 0
1D8A Frequency for Source 6 2 to 90 Hz 0.001 F003 0
Breaker Flashover (Read/Write Setting) (2 Modules)
2196 Breaker Flashover 1 Function 0 to 1 --- 1 F102 0 (Disabled)
2197 Breaker Flashover 1 Side 1 Source 0 to 5 --- 1 F167 0 (SRC 1)
2198 Breaker Flashover 1 Side 2 Source 0 to 6 --- 1 F211 0 (None)
2199 Breaker Flashover 1 Status Closed A 0 to 4294967295 --- 1 F300 0
219B Breaker Flashover 1 Status Closed B 0 to 4294967295 --- 1 F300 0
219D Breaker Flashover 1 Status Closed C 0 to 4294967295 --- 1 F300 0
219F Breaker Flashover 1 Voltage Pickup Level 0 to 1.5 pu 0.001 F001 850
21A0 Breaker Flashover 1 Voltage Difference Pickup Level 0 to 100000 V 1 F060 1000
21A2 Breaker Flashover 1 Current Pickup Level 0 to 1.5 pu 0.001 F001 600
21A3 Breaker Flashover 1 Pickup Delay 0 to 65.535 s 0.001 F001 100
21A4 Breaker Flashover 1 Supervision Phase A 0 to 4294967295 --- 1 F300 0
21A6 Breaker Flashover 1 Supervision Phase B 0 to 4294967295 --- 1 F300 0
21A8 Breaker Flashover 1 Supervision Phase C 0 to 4294967295 --- 1 F300 0
21AA Breaker Flashover 1 Block 0 to 4294967295 --- 1 F300 0
21AC Breaker Flashover 1 Events 0 to 1 --- 1 F102 0 (Disabled)
21AD Breaker Flashover 1 Target 0 to 2 --- 1 F109 0 (Self-Reset)
21AE Reserved (4 items) --- --- --- F001 0
21B2 ...Repeated for breaker flashover 2
Passwords Unauthorized Access (Read/Write Command)
2230 Reset Unauthorized Access 0 to 1 --- 1 F126 0 (No)
Field Unit Raw Data Settings (Read/Write Setting)
2460 Field Raw Data Port 0 to 7 --- 1 F244 6 (H1a)
2461 Field Raw Data Freeze 0 to 1 --- 1 F102 0 (Disabled)
Remote Double-Point Status Inputs (Read/Write Setting Registers) (5 Modules)
2540 Remote Double-point Status Input 1 Device 1 to 32 --- 1 F001 1
2541 Remote Double-point Status Input 1 Item 0 to 64 --- 1 F606 0 (None)
2542 Remote Double-point Status Input 1 Name 1 to 64 --- 1 F205 "RemDPS Ip 1"
2548 Remote Double-point Status Input 1 Events 0 to 1 --- 1 F102 0 (Disabled)
2549 ... Repeated for double-point status input 2
2552 ... Repeated for double-point status input 3
255B ... Repeated for double-point status input 4
2564 ... Repeated for double-point status input 5
IEC 61850 GGIO5 Configuration (Read/Write Setting Registers) (16 Modules)
26D0 IEC 61850 GGIO5 uinteger Input 1 Operand --- --- --- F612 0
26D1 IEC 61850 GGIO5 uinteger Input 2 Operand --- --- --- F612 0
26D2 IEC 61850 GGIO5 uinteger Input 3 Operand --- --- --- F612 0
26D3 IEC 61850 GGIO5 uinteger Input 4 Operand --- --- --- F612 0
26D4 IEC 61850 GGIO5 uinteger Input 5 Operand --- --- --- F612 0
26D5 IEC 61850 GGIO5 uinteger Input 6 Operand --- --- --- F612 0
26D6 IEC 61850 GGIO5 uinteger Input 7 Operand --- --- --- F612 0
26D7 IEC 61850 GGIO5 uinteger Input 8 Operand --- --- --- F612 0
26D8 IEC 61850 GGIO5 uinteger Input 9 Operand --- --- --- F612 0
Table B–9: MODBUS MEMORY MAP (Sheet 10 of 66)
ADDR REGISTER NAME RANGE UNITS STEP FORMAT DEFAULT