4–2 869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
SETPOINTS MAIN MENU CHAPTER 4: SETPOINTS
Figure 4-1: Main Setpoints Display Hierarchy
Figure 4-2: Main Setpoints Screen
Setpoints Entry Methods
Before placing the relay in operation, setpoints defining system characteristics, inputs,
relay outputs, and protection settings must be entered, using one of the following
methods:
Front panel, using the keypad and the display.
Front USB port, connected to a portable computer running the EnerVista 8 Series
Se
tup software.
Rear Ethernet (copper or fiber port connected to portable computer running the
EnerV
ista 8 Series Setup software.
Wi-Fi wireless connection to a portable comput
er running the EnerVista 8 Series Setup
software.
Rear RS485 port and a SCADA system running user-written software.
Any of these methods can be used to enter the same information. A computer, however,
makes
entry much easier. Files can be stored and downloaded for fast, error free entry
when a computer is used. To facilitate this process, the GE EnerVista CD with the EnerVista
Setpoints
Device
System
Inputs
Outputs
Protection
Monitoring
Control
Flexlogic
Testing