EasyManua.ls Logo

GE MI-869

GE MI-869
552 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL A–1
869 Motor Protection System
Appendix A
GE
Grid Solutions
Appendix A
Application Notes
Contactor Current Supervision
In some cases, the fault current can exceed the current which the contactor is rated to
interrupt. If such a condition has been detected, the 869 blocks the operation of the output
relay 1 “Trip” and operates a selected auxiliary output relay. The same auxiliary output
relay has to be wired to the upstream switching device (usually a breaker) that is rated to
interrupt the fault current. Finally, if the current has not decreased below the contactor
rated current for a programmable time, the block to the output relay 1 is removed.
The sequence described above is intended to pr
event damages to the contactor. In order
to use this sequence, the user has to configure the IOC 1 protection element, build a
FlexLogic Equation and configure output relays “Trip” and “Auxiliary”.
In the example below, Auxiliary output relay 4 has to be wired to the upstream switching
device.
1. IOC 1 configuration
Function = Configurable
Input = RMS
Pickup = [Contactor rated current, e.g. 10.000 x CT]
Direction = Disabled
Pickup Delay = [Duration of Trip r
elay block, e.g. 1.000 s]
Dropout Delay = 0.000
Block = Off
Output Relay 4 = Disabled
Events = Enabled
Targets = Latched

Table of Contents

Related product manuals