4–26 869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
DEVICE CHAPTER 4: SETPOINTS
Table 4-7: Data Written to Relay to Login as Administrator
Table 4-8: Login as Administrat
or Function Format
Table 4-9: Login as Administrat
or Function Format continued
Commands using Modbus Function 10H (Store Multiple Setpoints)
Sending commands requires writing 4 bytes to the Command address register using the
Modbus Fu
nction 10H (Store Multiple Setpoints). The 4 bytes are the function and the
command values. The function value is always 05.
Table 4-10: Modbus Commands registers
Description Memory Map Address Value to be written
DEC HEX DEC HEX
Role Characters 1 and 2 62242 F322 16740 4164
Role Characters 3 and 4 62243 F323 28009 6D69
Role Characters 5 and 6 62244 F324 28265 6E69
Role Characters 7 and 8 62245 F325 29556 7374
Role Characters 9 and 10 62246 F326 29281 7261
Role Characters 11 and 12 62247 F327 29807 746F
Role Characters 13 and 14 62248 F328 29184 7200
Role Characters 15 and 16 62249 F329 0 0000
Role Characters 17 and 18 62250 F32A 0 0000
Role Characters 19 and 20 62251 F32B 0 0000
Role Characters 21 and 22 62252 F32C 0 0000
Password Characters 1 and 2 62253 F32D 12288 3000
Password Characters 3 and 4 62254 F32E 0 0000
Password Characters 5 and 6 62255 F32F 0 0000
Password Characters 7 and 8 62256 F330 0 0000
Password Characters 9 and 10 62257 F331 0 0000
Password Characters 11 and 12 62258 F332 0 0000
Password Characters 13 and 14 62259 F333 0 0000
Password Characters 15 and 16 62260 F334 0 0000
Password Characters 17 and 18 62261 F335 0 0000
Password Characters 19 and 20 62262 F336 0 0000
Password Characters 21 and 22 62263 F337 0 0000
Slave# Function Data
Starting
Address
Number
of
Setpoints
Byte
Count
Data 1 Data 2 Data 3 Data 4 Data 5 Data 6 Data 7 Data 8 Data 9
FE 10 F322 0016 2C 4164 6D69 6E69 7374 7261 746F 7200 0 0
Data 10 Data 11 Data 12 Data 13 Data 14 Data 15 Data 16 Data17 Data 18 Data 19 Data 20 Data 21 Data 22
0 0 3000 0 0 0 0 0 0 0 0 0 0
Description Memory Map Address
DEC HEX
Command Register 40129 0x0080
Command Function Register 40130 0x0081