CHAPTER 4: SETPOINTS PROTECTION
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–141
Figure 4-44: Mechanical Jam logic diagram
89$.cdr
SETPOINT
Configurable
FUNCTION:
Disabled=0
Trip
Alarm
Latched Alarm
OR
SETPOINT
BLOCK:
Off=0
IA mag
IB mag
IC mag
AND
RUN
PICKUP:
SETPOINT
IA > Pickup
IB > Pickup
IC > Pickup
OR
PICKUP DELAY:
SETPOINTS
DROPOUT DELAY:
t
PKP
t
RST
FLEXLOGIC OPERAND
Mechanical Jam PKP
AND AND AND
Operate Output
Relay 1(TRIP)
LED: TRIP
OR
LED: ALARM
LATCH
S
R
RESET
Command
FLEXLOGIC OPERAND
Mechanical Jam OP
SETPOINT
OUTPUT RELAY X
Do Not Operate, Operate
Phase Currents Magnitude
from Phase Current CT bank
Motor Starting
FLEXLOGIC OPERAND
From Setpoint > System
> Motor > Setup
Speed2 Motor Switch
FLEXLOGIC OPERAND
I
avg
> OL x FLA
MOTOR OVERLOAD FACTOR:
SETPOINTS
SPEED2 MOTOR FLA:
LATCH
S
R
RUN
()ICIBIA
avg
I ++´=
3
1
IA RMS
IB RMS
IC RMS
RMS Phase Currents from
Phase Current CT bank
OR
SETPOINT
FUNCTION:
Disabled=0
AND
From Setpoint > Protection >
Motor > Acceleration time
ACCEL TIME FR. SPD 1-2:
SETPOINT
From Setpoint > Protection >
Motor > Sped2 Acceleration
Time
t
reset
0
AND
Rising Edge
AND
1 sec