4–164 869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
PROTECTION CHAPTER 4: SETPOINTS
ALARM PICKUP
Range: 1 to 25000 kW in steps of 1 kW
Default: 2 kW
The setting specifies a pickup threshold for the alarm function. The alarm pickup
threshold must be less than the motor load during normal operation.
ALARM DROPOUT DELAY
Range: 0.00 to 180.00 s in steps of 0.01 s
Default: 0.01 s
The setting specifies a time delay to reset the alarm command.
ALARM OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate
Any assignable output relay can be selected to operate upon Underpower operation.
BLOCK
Range: FlexLogic Operand
Default: Off
The Underpower can be blocked by any asserted FlexLogic operand.
EVENTS
Range: Enabled, Disabled
Default: Enabled
TARGETS
Range: Self-reset, Disabled
Default: Latched