CHAPTER 4: SETPOINTS PROTECTION
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–233
Figure 4-83: Volts per Hertz logic diagram
894010$ 1.cdr
Volts/Hz 1 PKP
FLEXLOGIC OPERAND
Pickup:
SETPOINTS
RUN
Curve:
TD Multiplier:
Reset Time:
Block:
SETPOINT
Off=0
AND
Volts/Hz 1 OP
t
V/ H z
SETPOINTS
Configurable
FUNCTION:
Disabled=0
Trip
Alarm
Latched Alarm
OR
AN D AND AND
Operate Output
Relay 1(TRIP)
LED: TRIP
OR
LED: ALARM
LATCH
S
R
RESET
Command
FLEXLOGIC OPERAND
SETPOINT
Relays
Do Not Operate, Operate
SIGNAL INPUT:
SETPOINT
Phase Voltage Inputs from Ph VT
Bnk1-J2
MAX
WYE Delta
Van
Vbn
Vcn
Vab
Vbc
Vca
Auxiliary Voltage Inputs from Aux
VT Bnk1-J2
Ph VT
Bnk1-J2
Aux VT
Bnk1- J2
J2-3VT Frequency
Actual Values
Actual Values
J2-Vx Frequency
V, F
V, F
Voltage Mode:
Vx