4–264 869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
MONITORING CHAPTER 4: SETPOINTS
Figure 4-102: Trip Circuit Monitoring Diagram
89$1.cdr
SETPOINT
TCM
FUNCTION:
Disabled
Alarm
OR
OR
AND
Latched Alarm
LED: ALARM /
LATCHED ALARM
RESET
Command
AND
S
R
LATCH # 1
Set-
Dominant
Configurable
FlexLogic Operand
Trip Coil Mon 1 OP:
SETPOINTS
Do Not Operate , Operate
OUTPUT RELAY
X
SETPOINT
TCM
BLOCK :
Off = 0
AND
SETPOINT
TCM
PICK
-
UP DELAY :
SETPOINT
TCM
BYPASS BKR STATE
:
Disabled = 0
FlexLogic Operand
Trip Coil 1 Mon PKP:
OR
t PKP
t RST
TCM
DROP-OUT DELAY:
SETPOINT
TCM
BKR STATUS CLOSED:
Off = 0
AND
OUTPUT RLY #1
“TRIP” OPERATE
OUTPUT RLY #1
MONITORING VOLTAGE <
THRESHOLD