CHAPTER 4: SETPOINTS MONITORING
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–269
Figure 4-105: Breaker Arcing Current logic diagram
SETPOINTS
BKR 1 ARCING
FUNCTION :
Alarm
Latched Alarm
OR
AND
LED: ALARM /
LATCHED ALARM
Command
AND
S
R
LATCH # 1
Set-
Dominant
Configurable
FlexLogic Operands
BKR 1 Arc OP
SETPOINTS
Do Not Operate, Operate
OUTPUT RELAY X
CT Bank current IB
CT Bank current IC
AND
SETPOINTS
BKR 1 ARCING
BLOCK :
Off = 0
CT Bank current IA
Disabled
AND
COMMAND
CLEAR BKR 1 ARCING
CURRENT :
YES = 1
OR
RESET
IA
²
t Integrate
IB
²
t Integrate
IC
²
t Integrate
RUN
RUN
RUN
SETPOINTS
BKR 1 ARCING
DELAY:
t
delay
0
BKR 1 ARCING
INITIATION:
Off = 0
SETPOINTS
OR
100ms
0
IA
²
cycle
IB
²
cycle
IC
²
cycle
Add to accumulator
Set all to 0
Select highest value
BKR 1 ARCING
CURRENTS
RECORDS
SETPOINTS
BKR 1 ARCING
ALARM LEVEL :
kA
²
cyc > Alarm Level
NO = 0
Total I
²
cycle