CHAPTER 4: SETPOINTS MONITORING
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–299
Figure 4-117: Pulsed Outputs logic diagram
SETPOINT
FUNCTION :
Enabled
FlexLogic Operands
Pos Wthrs Pulse OP
SETPOINTS
OUTPUT RELAY X
Disabled
Wh >= Whprev + PWhP
value
Whprev
RUN
Wh (kWh, MWh)
REAL ENERGY
POSITIVE Wh
ACTUAL VALUE
SETPOINT
POS WATTHOURS PULSE
VALUE
STORING Wh AT PULSE
Do Not Operate, Operate
RUN
FlexLogic Operands
Neg Wthrs Pulse OP
SETPOINTS
OUTPUT RELAY X
Wh >= Whprev + NWhP
value
Whprev
RUN
Wh (kWh, MWh)
REAL ENERGY
NEGATIVE Wh
ACTUAL VALUE
SETPOINT
NEG WATTHOURS PULSE
VALUE
STORING Wh AT PULSE
Do Not Operate, Operate
RUN
FlexLogic Operands
Pos Varhrs Pulse OP
SETPOINTS
OUTPUT RELAY X
VARh <= VARhprev -
PVARhP value
VARhprev
RUN
VARh (kVARh, MVARh)
REACTIVE ENERGY
POSITIVE VARh
ACTUAL VALUE
SETPOINT
POS VARHOURS PULSE
VALUE
STORING VARh AT
PULSE
Do Not Operate, Operate
RUN
FlexLogic Operands
Neg Varhrs Pulse OP
SETPOINTS
OUTPUT RELAY X
VARh <= VARhprev -
NVARhP value
VARhprev
RUN
VARh (kVARh, MVARh)
REACTIVE ENERGY
NEGATIVE VARh
ACTUAL VALUE
SETPOINT
NEG VARHOURS PULSE
VALUE
STORING VARh AT
PULSE
Do Not Operate, Operate
RUN
1 s 1 s
1 s 1 s
1 s 1 s
1 s 1 s
89$1.cdr