CHAPTER 4: SETPOINTS MONITORING
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–301
SET TO PRE-SET
Range: Off, Any operand from the list of FlexLogic operands
Default: Off
The setpoint selects the FlexLogic operand, digital input, virtual input or remote input
used to set the counter to the pre-set value. The counter is set at pre-set value in the
following situations:
1. When the Counter is enabled and Digital Counter 1 Set to Pre-Set operand has value 1
(when the Counter is enabled and Digital Counter 1 Set to Pre-Set operand has value
0, the Counter will be set to 0).
2. When the Counter is running and Digital Counter 1 Set to Pre-Set operand changes
the state from 0 to 1 (Digital Counter 1 Set to Pre-Set changing from 1 to 0 while the
Counter is running has no effect on the count).
3. When a reset or reset/freeze command is sent to the Counter and Digital Counter 1
Set to Pre-Set operand has the value 1 (when a reset or reset/freeze command is sent
to the Counter and Digital Counter 1 Set to Pre-Set operand has the value 0, the
Counter will be set to 0).
RESET
Range: Off, Any operand from the list of FlexLogic operands
Default: Off
The setpoint selects the FlexLogic operand, digital input, virtual input or remote input for
setting the count, either 0 or the pre-set value depending on the state of the Counter 1
Set to Pre-set operand.
FREEZE/RESET
Range: Off, Any operand from the list of FlexLogic operands
Default: Off
The setpoint selects the FlexLogic operand, digital input, virtual input or remote input for
freezing (capturing) the accumulating count value into a separate register with the
associated date and time of the operation while resetting the count to to either 0 or the
pre-set value depending on the state of the Counter 1 Set to Pre-set operand.
FREEZE/COUNT
Range: Off, Any operand from the list of FlexLogic operands
Default: Off
The setpoint selects the FlexLogic operand, digital input, virtual input or remote input for
freezing (capturing) the accumulating count value into a separate register with the
associated date and time of the operation while continuing counting. The present
accumulated value and frozen (captured) value with the associated date/time stamp are
available as STATUS values. If control power is interrupted, during the power-down
operation, the accumulated and frozen (captured) values are saved into non-volatile
memory.
HI OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate
EQL OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate
LO OUTPUT RELAY X
Range: Do Not Operate, Operate
Default: Do Not Operate