CHAPTER 4: SETPOINTS MONITORING
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–303
Figure 4-118: Digital Counter logic diagram
SETPOINT
DGTL CNTR 1
FUNCTION:
Disabled
Enabled
FlexLogic Operand
COUNTER 1 EQL
CALCULATE
ACCUMULATED VALUE
SETPOINTS
Do Not Operate, Operate
SETPOINTS
DGTL CNTR 1 PRE-SET:
SETPOINT
DGTL CNTR 1
BLOCK:
OFF=0
AND
SETPOINT
DGTL CNTR 1
UP:
OFF=0
SETPOINT
DGTL CNTR 1
DOWN:
OFF=0
SETPOINT
DGTL CNTR 1
SET TO PRE-SET:
OFF=0
SETPOINT
DGTL CNTR 1
RESET:
OFF=0
SETPOINT
DGTL CNTR 1
FREEZE/RESET:
OFF=0
SETPOINT
DGTL CNTR 1
FREEZE/COUNT:
OFF=0
OROR
AND AND
SET TO PRE-SET VALUE
SET TO 0
RUN
STORE DATE AND TIME
SETPOINT
DGTL CNTR 1
COMPARE:
COUNT = COMPARE
COUNT < COMPARE
DGTL CNTR 1 NAME:
DGTL CNTR 1 UNITS:
COUNT > COMPARE
FlexLogic Operand
COUNTER 1 LOW
SETPOINTS
Do Not Operate, Operate
FlexLogic Operand
COUNTER 1 HI
SETPOINTS
Do Not Operate, Operate
CNTR 1 HI
OUTPUT RELAY X
CNTR 1 EQL
OUTPUT RELAY X
CNTR 1 LOW
OUTPUT RELAY X
RECORDS
COUNTER 1 FROZEN
COUNTER 1 FROZEN
DATE AND TIME
COUNTER 1
ACCUMULATION
FlexLogic Operand
COUNTER 1 LIMIT
COUNTER REACHED
LIMITS
89$1.cdr