4–306 869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
MONITORING CHAPTER 4: SETPOINTS
Figure 4-119: Harmonic Detection logic diagram
894001$1.cdr
LED: PICKUP
SETPOINT
BLOCK :
Off=0
AND
SETPOINT
FUNCTION :
Disabled
Alarm
Latched Alarm
Configurable
OR
SETPOINT
PICKUP :
HMA PICKUP
RUN
SETPOINT
PICKUP DELAY :
t
PKP
0
Harm Det 1 OP
FlexLogic Operands
Harm Det 1 PKP
AND AN D
Command
RESET
OR
LED: ALARM
SETPOINT
MINIMUM OPER
CURRENT :
IA MINIMUM
RUN
S
LATCH
Set-
Dominant
R
Phase A Current (IA)
Phase B Current (IB)
Phase C Current (IC)
Phase A HM (HMA)
Phase B HM (HMB)
Phase C HM (HMC)
IB MINIMUM
IC MINIMUM
HMB PICKUP
RUN
HMC PICKUP
RUN
SETPOINT
OUTPUT RELAYS 1(X):
Do Not Operate , Operate
SETPOINT
INPUT :
SETPOINT
HARMONIC :
Average HM (HMavg)
Average Current (Iavg ) Iavg MINIMUM
HMavg PICKUP
RUN
SETPOINT
PHASES FOR
OPERATION :
ANY ONE : At least one
phase picked up ;
ANY TWO: Two or more
phases picked up;
ALL THREE: All three
phases picked up;
AVERAGE: Average value
picked up.