CHAPTER 4: SETPOINTS CONTROL
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–321
ACTIVE SETPOINT GROUP
Range: 1,2,3,4,5,6
Default: 1
The Active Setpoint Group setting is used for manual selection of the Active Setpoint
Group by setting.
SET GROUP 2 (3,4,5,6) ACTIVE
Range: Off, Any operand from the list of FlexLogic operands
Default: Off
The setpoint selects the FlexLogic operand, digital input, virtual input or remote input
that initiates change of the Active Setpoint Group.
GROUP CHANGE INHIBIT 1 (UP TO 16)
Range: Off, Any operand from the list of FlexLogic operands
Default: Off
The setpoint selects the FlexLogic operand, digital input, virtual input or remote input
that inhibits change of the active setpoint group.
EVENTS
Range: Disabled, Enabled
Default: Enabled