CHAPTER 4: SETPOINTS CONTROL
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–335
LOCAL START
Range: Off, Pushbutton 1 ON, Pushbutton 2 ON, Pushbutton 3 ON
Default: Pushbutton 1 ON
The setpoint is active, when the Local Mode is activated. The START command can be
initiated by the selected faceplate pushbutton. If any starter element is enabled, the
START command is generated by that element.
FAST PATH:
The START command operates Output relay 2 if
Setpoint > System > Contactor > Contactor
1 > Close Relay Select
is set to “Relay 2”.
REMOTE STOP
Range: Off, On, Any operand from the list of FlexLogic operands
Default: Off
The setpoint is active, when the Local Mode is inactive. This setpoint specifies the input
that when asserted, initiates a “STOP” command. When the selected input is asserted,
the output relay #1 is energized and stays energized until the input drops off, the breaker
(or contactor) opens, and the selected Seal-in time expires. This setpoint provides
flexibility to operate the output relay #1 by selecting an operand from the list of
FlexLogic operands, contact inputs, virtual inputs, or remote inputs. For example, the
operand “Phase OV 1 OP” can be selected to activate the output relay #1 according to
the operate conditions configured under the Phase OV 1 menu.
REMOTE START
Range: Off, On, Any operand from the list of FlexLogic operands
Default: Off
The setpoint is active, when the Local Mode is inactive. This setpoint specifies the input
that when asserted, initiates a START command. The setpoint provides flexibility to
operate the designated output relay by selecting an operand from the list of FlexLogic
operands, contact inputs, virtual inputs, or remote inputs. If any starter element is
enabled, the START command is generated by that element.
FAST PATH:
The START command operates Output relay 2 if
Setpoint > System > Contactor > Contactor
1 > Close Relay Select
is set to “Relay 2”.
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset