4–338 869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
CONTROL CHAPTER 4: SETPOINTS
Figure 4-139: Trip Bus logic diagram
Disabled = 0
SETPOINTS
TRIP BUS 1
INPUT 1:
Off = 0
SETPOINTS
TRIP BUS 1
FUNCTION :
Disabled
Trip
Operate Output Relay 1 (TRIP)
LED: TRIP
Alarm
OR
OR
AND
Latched Alarm
AND
SETPOINTS
TRIP BUS 1
BLOCK :
Off = 0
LED: ALARM /
LATCHED ALARM
Command
AND
S
R
LATCH
SET-
DOMINANT
Configurable
FlexLogic Operands
Trip Bus 1 OP
SETPOINTS
TRIP BUS 1
LATCHING:
Disabled = 0
SETPOINTS
TRIP BUS 1
PICKUP DELAY:
TRIP BUS 1
DROPOUT DELAY:
t
PKP
t
DPO
SETPOINTS
Do Not Operate, Operate
RELAYS
SETPOINTS
TRIP BUS 1
INPUT 2 :
Off = 0
SETPOINTS
TRIP BUS 1
INPUT 16 :
Off = 0
OR
. . .
. . .
RESET
AND
SETPOINTS
TRIP BUS 1
RESET:
OR
S
R
LATCH
SET-
DOMINANT
NON VOLATILE
Trip Bus 1 PKP
FlexLogic Operands
LED: PICKUP
89$.cdr