CHAPTER 4: SETPOINTS CONTROL
869 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL 4–343
Figure 4-140: Breaker Failure logic diagram
894067A2.cdr
SETPOINTS
BF 1
FUNCTION:
Alarm
Latched Alarm
OR
AND
Re-trip
LED: ALARM /
LATCHED ALARM
Command
AND
S
R
LATCH # 1
Set-
Dominant
Configurable
FlexLogic Operands
BF1 Highset OP
SETPOINTS
Do Not Operate, Operate
OUTPUT RELAYS
IA > PICKUP
IB > PICKUP
IC > PICKUP
IB
IC
RUN
RUN
RUN
AND
SETPOINTS
BF1
BLOCK :
Off = 0
OR
IA
AND
FlexLogic Operand
BF1 Retrip
Disabled
Operate Output
Relay 1 (TRIP)
LED: TRIP
AND
IN > PICKUP
RUN
SETPOINTS
BF1 PH RETRIP
SUPERV PICKUP:
BF1 NTRL RETRIP
SUPERV PICKUP:
IN
AND
OR
SETPOINT
BF1
BREAKER CLOSED:
Off = 0
OR
RESET
SETPOINTS
BF1
SUPERVISION :
Current
52b & Current
52b
AND AND
IA > PICKUP
IB > PICKUP
IC > PICKUP
RUN
RUN
RUN
IN > PICKUP
RUN
SETPOINTS
BF1
PHASE HIGHSET PICKUP:
BF1
NTRL HIGHSET PICKUP:
IA > PICKUP
IB > PICKUP
IC > PICKUP
RUN
RUN
RUN
IN > PICKUP
RUN
BF1
PHASE LOWSET PICKUP:
BF1
NTRL LOWSET PICKUP:
SETPOINTS
BF1
T1 PICKUP DELAY:
t1
PKP
0
SETPOINTS
BF1
T2 PICKUP DELAY:
t2
PKP
0
SETPOINTS
BF1
T3 PICKUP DELAY:
t3
PKP
0
SETPOINTS
BF1
LOWSET DELAY:
t
LOW
0
SETPOINTS
BF1
DROPOUT DELAY:
0
T
DPO
OR OR
OR
BF1 Lowset OP
BF1 OP
FlexLogic Operands
BF1 52b Superv OP
BF1 INITIATE:
EXTERNAL INITIATE
INITIATE IN1
...
INITIATE IN15
OR
SETPOINTS
SETPOINTS
SIGNAL INPUT:
USED ONLY IN
845 & 889
CT Bank 1 - J1
845
&
889
only
Relay ( Ready = 1)
BKR 1: Trip Relay
Select
Setpoints/System/
Breakers/BKR1: