EasyManua.ls Logo

GE MiCOM P141 Agile - Page 22

GE MiCOM P141 Agile
668 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Figure 39: Modification of current pickup level for voltage restrained overcurrent protection 106
Figure 40: Voltage dependant overcurrent logic (Phase A to phase B) 107
Figure 41: Selecting the current threshold setting 109
Figure 42: Cold Load Pickup logic 111
Figure 43: Selective Logic 113
Figure 44: Selecting the timer settings 115
Figure 45: Negative Sequence Overcurrent logic - non-directional operation 117
Figure 46: Composite Earth Fault Start Logic 117
Figure 47: Negative Sequence Overcurrent logic - directional operation 118
Figure 48: Non-directional EF logic (single stage) 121
Figure 49: IDG Characteristic 122
Figure 50: Directional EF logic with neutral voltage polarization (single stage) 123
Figure 51: Directional Earth Fault logic with negative sequence polarisation (single stage) 124
Figure 52: Current level (amps) at which transient faults are self-extinguishing 125
Figure 53: Earth fault in Petersen Coil earthed system 125
Figure 54: Distribution of currents during a Phase C fault 126
Figure 55: Phasors for a phase C earth fault in a Petersen Coil earthed system 126
Figure 56: Zero sequence network showing residual currents 127
Figure 57: Phase C earth fault in Petersen Coil earthed system: practical case with resistance
pr
esent
128
Figur
e 58: Non-directional SEF logic 130
Figure 59: SEF Any Start Logic 131
Figure 60: EPATR B characteristic shown for TMS = 1.0 132
Figure 61: Types of directional control 132
Figure 62: Resistive components of spill current 133
Figure 63: Operating characteristic for Icos 134
Figure 64: Directional SEF with VN polarisation (single stage) 135
Figure 65: Current distribution in an insulated system with C phase fault 136
Figure 66: Phasor diagrams for insulated system with C phase fault 137
Figure 67: Positioning of core balance current transformers 138
Figure 68: Thermal overload protection logic diagram 140
Figure 69: Spreadsheet calculation for dual time constant thermal characteristic 141
Figure 70: Dual time constant thermal characteristic 141
Figure 71: Broken conductor logic 144
Figure 72: Blocked Overcurrent logic 146
Figure 73: Blocked Earth Fault logic 147
Figure 74: Simple busbar blocking scheme 147
Figure 75: Simple busbar blocking scheme characteristics 148
Figure 76: 2nd Harmonic Blocking Logic (POC Input) 150
Figure 77: 2nd Harmonic Blocking Logic (SEF Input) 151
Table of Figures P14x
xx P14xEd1-TM-EN-1

Table of Contents

Related product manuals