EasyManua.ls Logo

GE MiCOM P145 Agile - Figure 56: Zero Sequence Network Showing Residual Currents

GE MiCOM P145 Agile
668 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
It can be seen that:
The voltage in the faulty phase r
educes to almost 0V
The healthy phases raise their phase to earth voltages by a factor of Ö3
The triangle of voltages remains balanced
The charging currents lead the voltages by 90°
Using a core-balance current transformer (CBCT), the current imbalances on the healthy feeders can be measured.
They correspond to simple vector addition of I
A1
and I
B1
, I
A2
and I
B2
, I
A3
and I
B3
, and they lag the residual voltage
by exactly 90º.
The magnitude of the residual current I
R1
is equal to three times the steady-state charging current per phase. On
the faulted feeder, the residual current is equal to I
L
- I
H1
- I
H2
(C). This is shown in the zero sequence network
shown in the following figure:
V00640
I
ROF
= Residual current on faulted feeder
I
ROH
= Residual current on healthy feeder
IOF = IL IH1 IH2 IH3
I
ROF
= I
H3
+ I
OF
so:
I
ROF
= I
L
I
H1
I
H2
3X
L
I
L
-V
0
X
CO
IH3 IH2 IH1
Healthy feeders
Faulty feeder
I
ROF
I
ROH
I
ROH
I
OF
Figure 56: Zero sequence network showing residual currents
In practical cases, however, resistance is present, resulting in the following phasor diagrams:
P14x Chapter 6 - Current Protection Functions
P14xEd1-TM-EN-1 127

Table of Contents

Related product manuals