EasyManua.ls Logo

GE MiCOM P145 Agile - Circuit Breaker Fail Logic; Figure 102: Circuit Breaker Fail Logic - Three Phase Start

GE MiCOM P145 Agile
668 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4 CIRCUIT BREAKER FAIL LOGIC
V00634
Ext. Trip 3ph
Trip Command In
IA< Start
IB< Start
IC< Start
External Trip EF
IN< Start
External TripSEF
CBF SEF Trip
ISEF< Start
CBF NonI Trip
Volt Prot Reset
I< Only
CB Open & I<
Prot Reset & I<
All Poles Dead
Ext. Trip 3ph
Ext Prot Reset
I<Only
CB Open & I<
Prot Reset & I<
All Poles Dead
ZCD IA<
ZCD IC<
ZCD IB<
ZCD IN<
ZCD IN<
ZCD ISEF<
CBF3PhStart
CB Fail Alarm
1
&
&
1
1
IN< Start
1
1
1
1
&
&
1
&
&
S
R
D
Q
S
R
D
Q
S
RD
Q
S
RD
Q
S
R
D
Q
All latches are reset dominant and are triggered on the positive edge . If
the edge occurs while the reset is active , the detection of the edge is
delayed until the reset becomes non -active.
Note on SR Latches
Figure 102: Circuit Breaker Fail logic - three phase start
P14x Chapter 8 - CB Fail Protection
P14xEd1-TM-EN-1 187

Table of Contents

Related product manuals