The diagram shows the single-phase Load Blinder logic for phase A. The same principle applies to phases B and C.
The single phase Load Blinder logic is ver
y similar to the three-phase Load Blinder logic. The main differences are:
The single-phase function does not use positive sequence impedance, it uses normal impedance measurment. It
also does not use negative sequence overcurrent to block the function.
P14x Chapter 6 - Current Protection Functions
P14xEd1-TM-EN-1 155