EasyManua.ls Logo

GE NetworX NX-6V2 - Keypad Sounder Control Options; System Timers Configuration

GE NetworX NX-6V2
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
NX-6V2 Control 19
Segment 4:
1 = On if Fail To Communicate report enabled.
2 = On if Log Full report enabled.
3 = On if Autotest report enabled.
4 = On if Start/End programming report enabled.
5 = On if End Download report enabled.
6 = On if Sensor Low Battery report enabled.
7 = On if Sensor Missing report enabled.
8 = On if First to Open / Last to Close.
Segment 5:
1 = On enable Lost Clock service light.
2 = On enables Zone Doubling (requires NX-200 Zone Doubling Kit).
3 = On disables On-Board 6 zones.
4 = On will allow two trips on same cross-zone to activate an alarm.
5 = On will not allow zones that are force armed to report bypass.
6 = Reserved.
7 = Use internal crystal for clock.
8 = Disable Temporal Siren on Fire. NOTE: Do NOT disable for UL listed systems.
Segment 6:
1 = Enable 2 wire smoke.
2 = Reserved.
3 = Enable for Zone Activity in Hours (not Days)
4 = Enable Daylight Savings Time (DST)
5 = Reserved
6 = On to disable Clean Me report (At default, bit is OFF = enabled)
7 = On to disable Start/End Test report (At default, bit is OFF = enabled)
8 = Reserved.
Segment 7: Reserved
L 38 SWINGER SHUTDOWN COUNT 1............. numerical
Location 38 contains the number of trips during an arming cycle that the NX-6V2 will allow before bypassing a zone. The count
determination is described in the Glossary. Factory default is 1.
L 39 KEYPAD SOUNDER CONTROL 1............. feature select
Segment 1:
1 = On if keypad sounds for ATelephone Line Cut@ when the system is armed.
2 = On if keypad sounds for ATelephone Line Cut@ when disarmed.
3 = On if keypad sounds upon AC Power Failure.
4 = On if keypad sounds when a Low Battery is detected.
5 = On if keypad sounds during Cross Zone trip time.
6 = On if keypad sounds for zone and box tampers.
7 = Reserved.
8 = On if keypad sounds for expander trouble (required for UL installations).
L 40 SYSTEM TIMERS 14...........numerical
Location 40 contains the duration of various system timing functions. Example: If you desire the duration of the Dynamic Battery Test
to be 30 minutes, you should program [3]-[0]-[r] in segment 1 of this location. The [3]-[0] is the number of minutes, and the [r] stores
the data and moves to the next segment of this location.
NOTES FOR UL INSTALLATIONS
The "Listen-In" feature cannot be enabled for UL Listed systems.
The "Dynamic Battery Test" feature cannot exceed four (4) hours.
The dial delay shall be set to -0-.
Segment 1 - Dynamic Battery Test duration in minutes 0-255 minutes..................................... (0 = no test)
Segment 2 - AC Fail report delay in minutes 0-255 minutes. .................................................... (0 = no delay)
Segment 3 - Power Up Delay in seconds 0-60 seconds ...........................................................(0 = no power up delay)
Segment 4 - Siren Time in minutes 1-254 minutes.
Segment 5 - Telephone Line Cut delay in seconds 0-255 seconds........................................... (0 = no TLM)
Segment 6 - Cross Zone time in minutes 0-255 ........................................................................ (0 = no cross zoning)
Segment 7 - Chime time in 50 mS (1/20th second) increments from 0-12 seconds.................. (0 = follows zone 255 latched)
Segment 8 - Dial delay in seconds 15-255 seconds

Related product manuals