Appendix B - Settings and Signals
P54A/B/C/E
B26
P54xMED-TM-EN-1
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
This command resets all CB shots counters to zero
Res AROK by UI 07 96 Enabled
Disabled
Enabled
[Indexed String]
If Enabled, this allows the successful auto-reclose signal to be reset by user interface command Reset AROK Ind.
Res AROK by NoAR 07 97 Disabled
Disabled
Enabled
[Indexed String]
If Enabled, allows the successful autoreclose signal to be reset by autoreclosing being disabled
Res AROK by Ext 07 98 Disabled
Disabled
Enabled
[Indexed String]
If Enabled, allows successful autoreclose signal reset by external DDB input Ext Rst CBx AROK via PSL.
Res AROK by TDly 07 99 Disabled
Disabled
Enabled
[Indexed String]
If Enabled, allows successful autoreclose signal to reset after time AROK Reset Time
Res AROK by TDly 07 9A 1
From 1 to 9999 in steps of 1
[Courier Number (time-seconds)]
Reset time for successful autoreclose signal if Res AROK by TDly is set to Enabled
Res LO by CB IS 07 9B Enabled
Disabled
Enabled
[Indexed String]
If Enabled, allows reset of CB lockout state when CB is "In Service" (i.e. CB is closed for time > CB IS Time)
Res LO by UI 07 9C Enabled
Disabled
Enabled
[Indexed String]
If Enabled, allows reset of each CB lockout state by UI command
Res LO by NoAR 07 9D Disabled
Disabled
Enabled
[Indexed String]
If Enabled, allows reset of CB lockout state by selecting autoreclosing disabled
Res LO by ExtDDB 07 9E Disabled
Disabled
Enabled
[Indexed String]
If Enabled, allows reset of CB lockout state by external DDB input Ext Rst CBx AROK via PSL.
Res LO by TDelay 07 9F Disabled
Disabled
Enabled
[Indexed String]
If Enabled, allows reset of CB lockout state after time LO Reset Time
LO Reset Time 07 A0 1
From 1 to 9999 in steps of 1
[Courier Number (time-seconds)]
Reset time for CB lockout if Res LO by TDelay is set to Enabled
DATE AND TIME
08
00
This column contains Date and Time stamp settings
Date/Time
08
01
Displays the IED’s current date and time.
Date
08
N/A
01/01/1994
Displays the date. Front Panel Menu only
Time
08
N/A
0
Displays the time. Front Panel Menu only
Battery Status 08 06
Dead
Healthy
[Indexed String]
Displays whether the battery is healthy or not
Battery Alarm 08 07 Enabled
Disabled
Enabled
[Indexed String]
Enables or disables battery alarm. The battery alarm needs to be disabled when a battery is removed or not used
Primary Source
08
08
PTP
IRIG-B

Table of Contents