Appendix B - Settings and Signals
P54A/B/C/E
B182
P54xMED-TM-EN-1
MENU TEXT COL ROW DEFAULT SETTING AVAILABLE OPTIONS
DESCRIPTION
[Courier Number (time-seconds)]
Setting for the time delay for the second stage definite time element.
ISEF>2 TMS 3A 42 1
From 0.025 to 1.2 in steps of 0.005
[Courier Number (decimal)]
Setting for the time multiplier to adjust the operating time of the IEC IDMT characteristic.
ISEF>2 Time Dial 3A 43 1
From 0.01 to 100 in steps of 0.01
[Courier Number (decimal)]
Setting for the time multiplier to adjust the operating time of the IEEE/US IDMT curves.
ISEF>2 IDG Time 3A 44 1.2
From 1 to 2 in steps of 0.01
[Courier Number (time-seconds)]
Setting for the IDG curve used to set the minimum operating time at high levels of fault current.
ISEF>2 Reset Chr 3A 46 DT
DT
Inverse
[Indexed String]
Setting to determine the type of reset/release characteristic of the IEEE/US curves.
ISEF>2 tRESET 3A 47 0
From 0 to 100 in steps of 0.01
[Courier Number (time-seconds)]
Setting to determine the reset/release time for definite time reset characteristic.
ISEF>3 Status 3A 49 Disabled
Disabled
Enabled
[Indexed String]
Setting to enable or disable the third stage definite time sensitive earth fault element.
ISEF>3 Direction 3A 4A Non-Directional
Non-Directional
Directional Fwd
Directional Rev
[Indexed String]
This setting determines the direction of measurement for the third stage element.
ISEF>3 Current 3A 4D 0.4
From 0.005*I3 to 0.8*I3 in steps of 0.001*I3
[Courier Number (current)]
Pick-up setting for the third stage sensitive earth fault element.
ISEF>3 Delay 3A 4E 0.5
From 0 to 200 in steps of 0.01
[Courier Number (time-seconds)]
Setting for the operating time delay for third stage sensitive earth fault element.
ISEF>4 Status 3A 50 Disabled
Disabled
Enabled
[Indexed String]
Setting to enable or disable the fourth stage definite time sensitive earth fault element.
ISEF>4 Direction 3A 51 Non-Directional
Non-Directional
Directional Fwd
Directional Rev
[Indexed String]
This setting determines the direction of measurement for the fourth stage element.
ISEF>4 Current 3A 54 0.6
From 0.005*I3 to 0.8*I3 in steps of 0.001*I3
[Courier Number (current)]
Pick-up setting for the fourth stage sensitive earth fault element.
ISEF>4 Delay 3A 55 0.25
From 0 to 200 in steps of 0.01
[Courier Number (time-seconds)]
Setting for the operating time delay for fourth stage sensitive earth fault element.
ISEF> Blocking 3A 57 0x00F
VTS Blks ISEF>1
VTS Blks ISEF>2
VTS Blks ISEF>3
VTS Blks ISEF>4
A/R Blks ISEF>3
A/R Blks ISEF>4
[Binary Flag (8 bits)]
Logic Settings that determine whether blocking signals from VT supervision affect certain earth fault overcurrent stages.
VTS Block - only affects sensitive earth fault protection. With the relevant bit set to 1, operation of the Voltage Transformer Supervision (VTS),
will block the stage. When set to 0, the stage will revert to Non-directional upon operation of the VTS.
ISEF DIRECTIONAL
3A
58
Sensitive Earth Fault Directional Sub Heading