Appendix B - Settings and Signals
ORDINAL SIGNAL NAME ELEMENT NAME
DESCRIPTION
Block phase undervoltage stage 1 time delayed trip
Block phase undervoltage stage 2 time delayed trip
Block phase overvoltage stage 1 time delayed trip
Block phase overvoltage stage 2 time delayed trip
Block residual overvoltage stage 1 time delayed trip
Block residual overvoltage stage 2 time delayed trip
52-A (CB closed) CB auxiliary input (3 phase)
52-A (CB A phase closed) CB auxiliary
52-A (CB B phase closed) CB auxiliary
52-A (CB C phase closed) CB auxiliary
52-B (CB open) CB auxiliary input (3 phase)
52-B (CB A phase open) CB auxiliary input
52-B (CB B phase open) CB auxiliary input
52-B (CB C phase open) CB auxiliary input
Circuit breaker healthy (input to auto-recloser - that the CB has enough energy to allow re-closing)
VT supervision input - signal from external miniature circuit breaker showing MCB tripped
Initiate tripping of circuit breaker from a manual command
Initiate closing of circuit breaker from a manual command
Reset Manual CB Close Timer Delay (stop & reset Manual Close Delay time for closing CB).
Reset latched relays & LEDs
Reset thermal state to 0%
Manual control to reset auto-recloser from lockout
Reset CB Maintenance values
DDB mapped in PSL from opto or comms input. External signal to force CB autoreclose to lockout.
Pole discrepancy (from external detector) - input used to force a 3 pole trip on CB.
To enable loopback mode via opto input
DDB_PERMISSIVE_INTERTRIP_OPTO
Permissive intertrip mapping what will be sent to the remote line end
To enable stub bus protection, requires setting to enable feature.
DDB_INHIBIT_CURRENT_DIFF_OPTO
When linked to an opto input, inhibits differential relay at the local end and send an inhibit command to the remote end