P54A/B/C/E
Appendix B - Settings and Signals
P54xMED-TM-EN-1
B239
ORDINAL SIGNAL NAME ELEMENT NAME
DESCRIPTION
456
Recon Interlock
DDB_RECONFIGURATION_INTERLOCK
This must be energized (along with DDB 455 - inhibit C Diff) at the time that a relay configuration is changed from 3 ended to 2 ended
scheme. This usually should be driven from a 52-B contact of the CB connected to the line end that is taken out of service
459
Test Mode
DDB_TEST_MODE
Commissioning tests - automatically places relay in test mode
460
103 CommandBlock
DDB_COMMAND_BLOCKING
For IEC-870-5-103 protocol only, used for "Command Blocking" (relay ignores SCADA commands)
461
103 MonitorBlock
DDB_MONITOR_BLOCKING
For IEC-870-5-103 protocol only, used for "Monitor Blocking" (relay is quiet - issues no messages via SCADA port)
463
Inhibit I>1
DDB_INHIBIT_POC1
Inhibit stage 1 overcurrent protection
464
Inhibit I>2
DDB_INHIBIT_POC2
Inhibit stage 2 overcurrent protection
465
Inhibit I>3
DDB_INHIBIT_POC3
Inhibit stage 3 overcurrent protection
466
Inhibit I>4
DDB_INHIBIT_POC4
Inhibit stage 4 overcurrent protection
467
Inhibit IN>1
DDB_INHIBIT_EF1
Inhibit stage 1 earth fault protection
468
Inhibit IN>2
DDB_INHIBIT_EF2
Inhibit stage 2 earth fault protection
469
Inhibit IN>3
DDB_INHIBIT_EF3
Inhibit stage 3 earth fault protection
470
Inhibit IN>4
DDB_INHIBIT_EF4
Inhibit stage 4 earth fault protection
471
Inhibit V<1
DDB_INHIBIT_UV1
Inhibit stage 1 undervoltage protection
472
Inhibit V<2
DDB_INHIBIT_UV2
Inhibit stage 2 undervoltage protection
473
Inhibit V>1
DDB_INHIBIT_OV1
Inhibit stage 1 overvoltage protection
474
Inhibit V>2
DDB_INHIBIT_OV2
Inhibit stage 2 overvoltage protection
475
Inhibit VN>1
DDB_INHIBIT_RESOV1
Inhibit stage 1 residual overvoltage protection
476
Inhibit VN>2
DDB_INHIBIT_RESOV2
Inhibit stage 2 residual overvoltage protection
478
Inhibit Thermal
DDB_INHIBIT_THERMAL
Inhibit thermal overload protection
479
InhibitCB Status
DDB_INHIBIT_CBS
Inhibit circuit breaker state monitoring (no alarm for defective/stuck auxiliary contact)
480
Inhibit CB Fail
DDB_INHIBIT_CBF
Inhibit circuit breaker fail protection
481
Inh Broken Line
DDB_INHIBIT_BCL
Inhibit Broken conductor protection
482
Inhibit VTS
DDB_INHIBIT_VTS
Inhibit VT supervision (including turn OF MCB’s) via PSL
483
Inhibit CTS
DDB_INHIBIT_CTS
Inhibit CT supervision (both differential and standard CTS) via PSL
484
InhibitChecksync
DDB_INHIBIT_CHKSYN
Inhibit checksync. (Both stages and for each CB)
485
Inhibit TOR
DDB_INHIBIT_TOR
Inhibit trip on reclose (TOR)
486
Inhibit SOTF
DDB_INHIBIT_SOTF
Inhibit switch onto fault (SOTF)
487
Disable CTS
DDB_DISABLE_CTS
To disable differential CTS via PSL
488
Set SOTF
DDB_SET_SOTF