Chapter 6. Programming EGD Commands
96 PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual GFK-2224Q
6.5 Read PLC Memory (4000)
The Read PLC Memory command can be used to read memory locations from a remote PACSystems PLC. This
command does not require configuration of a produced / consumed exchange in the PLCs. The Read PLC
Memory command can only be sent to an individual IP Address; it cannot be sent to a Group ID (multicast).
Read PLC Memory Command Block
Length of command data block
Always 0 (no-wait mode request)
Memory type of COMMREQ Status Word
Offset of COMMREQ Status Word
Read PLC Memory command number.
Retry time, in milliseconds
The time between retries of command transfers. Default
is 1000ms.
Local read buffer memory type
Memory type for the data to be placed in the local PLC.
Local read buffer reference table
starting address (least significant
1-based offset in the local PLC
Local read buffer reference table
starting address (most significant
Remote read location memory type
Memory type from which data will be read in the remote
PLC
Remote reference table read
location starting address (least
1-based offset in the remote PLC
Remote reference table read
location starting address (most
Remote reference table length (in
remote memory units)
Number of remote memory units to be read.
Must be 1. Indicates an IP address will be used.
Must be 4 for IP address.
Group ID (multicast) is not permitted.
Word 21
IP Address of the remote PLC
Four integers, specified as one integer per word of the
dotted-decimal IP address of the remote PLC. May not
13
Word 4 (COMMREQ status word address) is the only zero-based address in the Command Block. This value
alone requires that 1 be subtracted from the intended address.