Chapter 12. Diagnostics
224 PACSystems* RX7i & RX3i TCP/IP Ethernet Communications User Manual GFK-2224Q
Error Status (Hexadecimal)
Minor Error Code Description
Client
I/O configuration is invalid.
No privilege for attempted operation.
Service request has been aborted.
Minor Error Codes for Major Error Code 11H (at Remote Server PLC)
SRTP Error Code Description
Unexpected SRTP version encountered in received message.
Unrecognized SRTP message received.
Data present in SRTP message, which should not contain data.
Generic resource problem detected.
SRTP message encountered in inappropriate connection state.
Generic refusal by backplane driver to handle request.
Recognized but unsupported SRTP message received.
Lost transaction in server.
Error sending SRTP PDU to the client PLC.
Unable to allocate a text buffer from dual port memory.
Invalid text length detected in a mailbox message.
Invalid number of destinations detected in a mailbox message.
Invalid source detected in a mailbox message.
Invalid slot number detected in a mailbox message.
Invalid rack number detected in a mailbox message.
Bad text buffer address in dual port memory.
Unable to find control data required to send a mailbox message to the PLC.
Timed out waiting for availability of mail communications with the PLC.
Invalid task ID detected while attempting to send a mailbox message to the PLC.
Unable to send mailbox message to PLC because the mail queue is full.
Unable to communicate with PLC.
Backplane driver not initialized or unable to acquire a dual port memory semaphore.
The backplane driver could not access the PLC.
Invalid binding on the message sent to the backplane driver.
The message could not be sent to its destination because the mailbox was not open.
The maximum number of transfers to the destination is already taking place.
The maximum number of transfers of this transfer type is already taking place.
Cannot obtain a backplane transfer buffer.
Cannot obtain resources other than backplane transfer buffers.
Connection ID or block transfer ID is not valid.
Timed out waiting for PLC CPU response.
The PLC CPU aborted the request.
An invalid message type was specified.
The specified task is not registered.