XMTC User’s Manual 13
Chapter 2. Installation
2.4.2 CE Mark Compliance
2.4.3 Cable Specifications
Table 1 below shows the transmitter wiring connections for the standard GE XMTC cable, P/N X4(10). This cable can
be used for distances up to 4000 ft (1200 m).
If you are using your own cable to wire the XMTC, refer to Table 2 below for the cable requirements.
WARNING! To meet CE Mark requirements, you must shield and ground all electrical cables as
described in Appendix E.
WARNING! CE Mark compliance is required for all units installed in EU countries.
WARNING! Cable entries of an approved flameproof design are required. These must be
installed according to the manufacturer’s instructions. The choice of cable entry device may limit
the overall installation category achieved.
Table 1: GE 4-Wire XMTC Cable
Lead Color AWG Terminal
+24 VDC Line Red 22 TB1-1
24 VDC Return Black 22 TB1-2
4-20 mA (+) White 22 TB1-3
4-20 mA (-) Green 22 TB1-4
Table 2: Non-GE 4-Wire XMTC Cable
Maximum Cable Length Wire Size
ft m AWG mm
2
450 130 22 0.35
700 200 20 0.60
1,050 320 18 1.00
1,700 500 16 1.20
2,800 850 14 2.00
4,000 1,200 12 3.00