ZP3 Fire Control Panel User Guide     
Routine maintenance 
Note:  Occupants of the building and anyone receiving remote alarm signals, such as the fire department, must be 
informed before starting with the test/routine maintenance. They must also be informed when the 
test/routine maintenance is complete. No alarms should be activated before notification has taken place. 
 
CAUTION: 
External systems connected to the fire system, such as fire extinguishing systems, air-
conditioning systems, or lifts must be temporarily disabled or disconnected BEFORE 
testing or routine maintenance takes place. 
 
 
WARNING: 
ALL DISCONNECTED OR DISABLED SYSTEMS MUST BE RECONNECTED AND/OR ENABLED 
AT THE END OF TESTING. 
Daily checks 
Do the following checks every day: 
1.  Check that the green Power-on indicator is illuminated. All other LED's should be off except 
the Common Disabled LED (depending on the system status, e.g. day mode) and the panel 
should be silent. The display should show the time and date only. 
2.  If the panel is indicating a fault alarm, contact the maintenance staff and arrange for the 
fault to be rectified. 
3.  Make sure the logbook (document number 503-1842ZE-0-02) is kept up-to-date. Check that 
all faults recorded in the logbook the previous day has been attended to. 
4.  Make sure that the correct time and date is displayed on the ZP3 panel. If not, then correct 
the time/date as described under Menu structure on page 22. 
Revision 11 (05/01/2010)    Page 27