8555-9201-000 / 0109 75
Mechanical Separation / GEA Westfalia Separator
4.30 Alarm #43 - PT2 sensor active when idling
PT2 SENSOR ACTIVE
WHEN IDLING
Alarm#431 ENTER
Text display Possible causes Action
Pressure transmitter PT2 was acti-
vated when idling.
Check pressure transmitter PT2.
Filling water valve V2 leaks.
Check V2.
Product valve V1 doesn’t close prop-
erly.
Check valve V1.
Non-return flap at V7 jams,
product runs back into the bowl.
Close clean oil discharge valve
(product discharge valve) V7 when
idling.
Help text information on the control system
ENT E R
Step 1 Acknowledge fault
HEL P
Step 2
Press key >F1<
Help on alarm
Key >HOME< back
Page 1
PT2 SENSOR ACTIVE
WHEN IDLING
Please check:
Pressure transmitter PT2
->
Page 2
V2 leakage
Product valve
V1 closes properly
Product runs back into
->
Page 3
bowl
back with ENTER
F1