- 23 -
INSTALLATION
3.3.3.8 - Examples of installations with a 45°
bend and a 90° bend at the boiler out
-
let
3.3.3.8.1 - Straight configuration
Accessories :
- 1 45° concentric elbow Ø 80/125
- 1 90° concentric elbow Ø 80/125,
- concentric extensions Ø 80/125,
- 1 concentric vertical terminal Ø 80/125,
- 1 vertical terminal fastening collar (supplied with
the vertical terminal),
- 1 sleeve tile adaptable according to the type of
roof covering and the roof slope,
- 1 roof plate,
- 3 Ø 125 fastening collars,
Note:
- Each 45° elbow added reduces the maximum
authorised length by 0.5 m.
- Each 90° elbow added reduces the maximum
authorised length by 1m.
3.3.3.8.2 - Straight configuration
Accessoires :
- 1 45° concentric elbow Ø 80/125
- 1 90° concentric elbow Ø 80/125,
- 3 concentric extensions Ø 80/125,
- 2 45° concentric elbow Ø 80/125,
- 1 concentric vertical terminal Ø 80/125,
- 1 vertical terminal fastening collar (supplied with
the vertical terminal),
- 1 sleeve tile adaptable according to the type of
roof covering and the roof slope,
- 1 roof plate,
- 3 Ø 125 fastening collars
Note:
- Each 45° elbow added reduces the maximum
authorised length by 0.5 m.
- Each 90° elbow added reduces the maximum
authorised length by 1m.
Lmax = L1 + 1 m + 0,5 ≤ 9 m
L
1
FCX-26-3
rear boiler
View from above
45° elbow
90° elbow
Fig. 36
Refer to section 3.1 - page 13 - chapter IV - INSTALLATION
for other outlet configurations
Lmax = L1 + 0,5 m + L2 + 0,5 m+ L3 + 1 m + 0,5
≤
9 m
L
1
L
2
L
3
FCX-27-3
rear boiler
View from above
45° elbow
90° elbow
Fig. 37
Refer to section 3.1 - page 13 - chapter IV - INSTALLATION
for other outlet configurations