44-00-0297 SHERLOCK102/202 REV. 4.1 05-02-15
31
This menu also shows the most recent 10 alarm logs.
At DEFAULT SCREEN, press UP/DOWN arrow button to
scroll to the "<ALARM MENU>". Press the SELECT button
to enter this menu.
Each successive screen will show the last 10 alarms in reverse
order. ie Last one first and the times the alarm was cleared.
ALMX refers to Alarm number X (X = 1 through 10)
Down Arrow to the next 10 logs
Exit menu and return to the DEFAULT SCREEN
SELECT/
CHANGE
<ALARM LOG M>
EXIT
ALARM LOG MENU
<ALMX> SNR A LVL 1
380 05/02 16:30
ALARM MESSAGE DESCRIPTION
There is no alarm condition for this entry in the alarm log. All entries show no alarm if
Alarm Log has been cleared in SYSTEM CONFIG MENU.
Sensor X was in alarm at Alarm level Y and reading XXX ppm on this date and time.
The previous alarm was cleared by the user on this date and time.
The previous alarm auto cleared by the control on this date and time.
Sensor X was opened, no sensor return current path was detected on this date and time.
Problem can either be a wiring problem, an incorrect style of sensor
Sensor A was an Oxygen Depletion Sensor and was in an alarm condition on this date
and time. This alarm will also activate if a refrigerant sensor is attached when the
oxygen sensor is selected from the configure menu.
<ALMX>SNR X LVL Y
380 1/06 02:32
<ALMX> AUTO CLEAR
AT 1/06 02:32
<ALMX> SNR X OPEN
AT 1/06 02:32
<ALMX> O2 SNR ALM
0.9% 1/06 02:32
<ALM1> NO ALARM
AT 00/00 00:00
<ALMX> USER CLEAR
AT 1/06 02:32