Placing and installing your roaster
Giesen W6A Coffee Roaster - Version 1.0 17
7.4 Gas connection
Only authorized skilled persons are allowed to connect the gas line! The installation
must confirm with local codes. When local codes are in absence use the National
Fuel Gas Code, ANSI Z223.1/NFPA54 or the Natural Gas and Propane Installation
Code, CSA B149.1.
• A manual gas shut-off valve must be installed at the roaster (for maintenance
and safe storage).
• Connection: 3/8” right thread standard fitting.
Gas type: see identification plate on the back side of the roaster.
USA / Canada gas connection statement - Only for USA / Canada installing
locations!
A statement that the installation must conform with local codes, or in the absence of
local codes, with the National Fuel Gas Code, ANSI Z223.1, Natural Gas Installation
Code, CAN/CGA-B149.1, or the Propane Installation Code, CAN/CGA-B149.2, as
applicable, including:
1. The appliance and its individual shutoff valve must be disconnected from the gas
supply piping system during any pressure testing of that system at test pressures
in excess of 1/2 psi (3.45 kPa).
2. The appliance must be isolated from the gas supply piping system by closing its
individual manual shutoff valve during any pressure testing of the gas supply
piping system at test pressures equal to or less than 1/2 psi (3.45 kPa).