10 Characteristic Values
1)
Display range up to 600 V
2)
Display range up to 1.2 kV
3)
the indicated accuracy is only achieved with the shielded high-resistance measur-
ing cable KS-C (article no. Z541F)“
Meas.
Qty.
U
iSO
Range Measuring Range
Reso-
lution
Test
Current
Intrinsic Uncertainty
Measuring
Uncertainty
Overload Capacity
RISO
50 V
100 V
G500(MM): 250 V / 500 V
G1000: 250 V / 500 V / 1000 V
100 k 10.0 k ... 99.9 k 0.1 k
I
N
= 1 mA
I
K
3.6 mA
(5% rdg. + 3 d) (7% rdg. + 3 d)
METRISO G500(MM):
600 V AC/DC TRMS
METRISO G1000:
1000 V AC/DC TRMS
1 M 100 k ... 999 k 1 k
10 M 1.00 M ... 9.99 M 10 k
100 M 10.0 M ... 99.9 M 100 k
1 G 100 M ... 999 M 1 M
10 G 1.00 G ... 9.99 G 10 M
100 G 10.0 G ... 99.9 G 100 M (8% rdg. + 3 d)
3)
(10% rdg. + 3 d)
3)
200 G 100 G ... 199 G 1 G (25% rdg. + 5 d)
3)
(50% rdg. + 20 d)
3)
U
AC/DC
METRISO G500
METRISO MM500
100 V 10.0 V ... 99.9 V 0.1 V
(2.5% rdg. + 3 d) (5% rdg. + 3 d) 600 V AC/DC TRMS
500 V 100 V ... 510 V
1)
1 V
METRISO G1000
100 V 10.0 V ... 99.9 V 0.1 V
(2.5% rdg. + 3 d) (5% rdg. + 3 d) 1000 V AC/DC TRMS
1000 V 100 V ... 999 V
2)
1 V
RLO
METRISO G500
METRISO G1000
10 0.17 ... 9.99
0.01
I
N
200 mA (2.5% rdg. + 3 d) (5% rdg. + 3 d)
METRISO G1000:
1000 V AC/DC TRMS
METRISO G500:
600 V AC/DC TRMS
R
Display range as of
01.0
100 10.0 ... 99.9 0.1
I
N
1 mA (2.5% rdg. + 3 d) (5% rdg. + 3 d)
METRISO G1000:
1000 V AC/DC TRMS
METRISO G500(MM):
600 V AC/DC TRMS
1 k 100 ... 999 1
10 k 1.00 ... 9.99 k 10