42
Fault Finding
12 Fault Finding
1
2.1 Burner Fault Finding Chart
1. Burner fails to start no flame no lock out
Symptoms Possible Causes Actions
Motor fails to run No electrical supply to boiler Check On/Off switch is On - mains neon is lit
Lock-out light not lit Fuse has blown Check or replace fuse
If fuse has blown - check reason for failure
Boiler thermostat not calling Adjust boiler thermostat to call for heat
Heating controls are not calling Adjust programmer & room thermostat to call
Overheat thermostat has operated Check and reset overheat thermostat if required
If operated - check reason for operation
No power to burner Check for 230V at control box mains terminals
Control box faulty Replace faulty control box
2. Burner fails to start no flame goes to lock out
Symptoms Possible Causes Actions
Motor fails to run No power to burner motor Check for 230V at motor plug terminals
Burner lock-out Burner motor capacitor faulty Check and replace if necessary
Burner motor faulty Replace burner motor
Burner motor stalled
Seized oil pump Check and replace faulty oil pump