Fig.3.3 Dimension of Electric Box Cover
3.1 Installation Requirements
(1) Communication cord of the centralized controller must be selected
according to the table below. Never use the cable that is not in compliance
with instructions of this manual.
Notice:
① The cord shall be Circular cord (the cores shall be twisted together).
② If unit is installed in places with intense magnetic field or strong
interference, it is necessary to use shielded wire.
(2) Never install the centralized controller in the following places:
1) Places with corrosive gas or serious dust, salt mist or oil smoke.
2) Wet and damp places, with direct sunlight.
3) Places near high temperature objects or places where units might be
splashed by water.