DC Inverter Multi
VRF Service Manual
DPOUSPM
7.1.3 Display View
PAGE
INDOOR UNIT
ERROR
AUTO
ROOM TEMP.
SWING SLEEP
MELT
TIMER
ON
OFF
SET TEMP.
ERR CODE
COOL
DRY
FAN
HEAT
AUTO
LOW
CHECK
MONITORING
DETECTING
TEST
MID
HIGH
CENTER
ADDRESS
INITIALIZE
SINGLE
SELECT
CTRL MODE
SYS
SET
IN-
DOOR
DO
MAIN
c c
Mon.
Tue.
Wed.
Thu.
Fri.
Sat.
Sun.
Year
MonD ate
Hour Min
1 32 4 5
6
1012 111314 915
16
8
7
Fig.7.1.3
1
Pagination/displays
present domain
Under select control mode, group no. that is present controlling is displayed;
Under addresses setting state, present Soft Add is displayed.
2 Present unit no.
Displays the soft address of communication module that the present checking or
controlling indoor unit is belonged as well as the address of indoor unit;
Format: Soft add—Indoor unit add
3 Error Displays when there is error at any indoor or outdoor unit.
4 Operation mode Displays every operation state mode of indoor unit
5 Speed display Displays High, Medium, Low and Auto speed of indoor unit
6 Check
Under group control mode, it is displayed when checking grouping information;
Under address setting mode, it is displayed when checking hard address.
7 Error code Displays when abnormal occur on operation state of present indoor unit.
8
Operation monitoring and
controlling /monitoring
When central control works in normal, operation monitoring displays; when control
signal is transmitted, operation monitoring and controlling is displayed.
9 System time Displays present time, format is Y, M, D, H, M and week.
10 Timer setting Timer On/Off on when Timer On/Off is set to present indoor unit
11 Pre-set temperature Displays value of pre-set temperature
12 Swing and Defrost Displays operation of swing at indoor unit and defrost at outdoor unit
13 Ambient temperature Displays value of ambient temperature of present indoor unit
14 System setting
Setting operation mode of central control. It should be completed
by installation personnel, but not for users.
15 Control mode Displays 3 control modes of Central, Single and Select controls
16 Displays of soft address
When Indoor on, addresses of present online indoor unit is displayed;
When domain on, soft address of present online communication module is displayed;
6SHFL¿FORFDWLRQRIFRQWUROOHGLQGRRUXQLWFDQRQO\EHDVFHUWDLQHG
:KHQVRIWDGGUHVV¿WV3URMHFW,QVWDOODWLRQ/LVW
Instruction to display interface:
System Setting: Including Address Setting and other functions, and it is set when installation personnel are
adjusting units. It is not recommended that users operate it. The usage of this function requires password.
$GGUHVV6HWWLQJ6LQFHFKDUDFWHUVIURPWRDUH¿[HGDVWKHDGGUHVVHVRIFRQWUROOLQJFRPPXQLFDWLRQ
modules displayed by central control (hereinafter called soft addresses), and the addresses of communication
modules themselves (hereinafter called hard addresses) are value from 0~254, thus there is address matching
problem between central control and controlled communication module. In order to solve this problem, address
mapping setting is required to be conducted before project adjusting!